All states / Arizona / R-11 / Study guide
How to pass the Arizona R-11 Electrical exam
A study guide for the Arizona R-11 Electrical exam: what it covers, how much each section counts, the rules that come up most, and a study plan. Rules below link to their official source wherever one exists.
The exam at a glance
- 110 questions, 240 minutes, 70% to pass (PSI).
- Open book: 2017 NEC, NFPA 72 (2016) and 29 CFR 1926.
Source: PSI content outline (R-11). Always confirm details with AZ ROC before test day.
What's on the exam
- Services, Feeders & Branch Circuits16%
- Grounding & Bonding15%
- Raceways & Boxes14%
- Conductors & Cables11%
- Photovoltaics9%
- Overcurrent Protection6%
- General Electrical Knowledge5%
- Lighting5%
- Fire Detection & Alarm5%
- Safety5%
- Special Occupancies & Equipment3%
- Motors3%
- Electrical Devices2%
- Low Voltage2%
Section weights from the official exam outline. Bigger sections are worth more points, so study them first.
A 4-step study plan
- Take a baseline test. Answer a full mock exam before studying so you know where you stand in each section.
- Study by weight, then by weakness. Start with Services, Feeders & Branch Circuits (16%), Grounding & Bonding (15%), Raceways & Boxes (14%), then move to whichever sections scored lowest on your baseline.
- Learn the rule, not just the answer. For every miss, read the explanation and the code section or statute it cites; on test day you'll need to know these references well.
- Repeat mock exams until you're consistently at 80% or more, which gives you a cushion above the passing score. Retake the questions you missed until they stick.
Key rules to know, by section
A few of the facts that come up in each section, with the answer and the source. The full course has 478 questions with explanations.
Services, Feeders & Branch Circuits 16% of the exam · 29 practice questions
- Four or more fastened-in-place appliances in a dwelling may be calculated at? 75%. Rule (NEC 2017 §220.53): a demand factor of 75% may be applied to the nameplate rating load of four or more appliances fastened in place, other than electric ranges, clothes dryers, space-heating equipment or air-conditioning equipment, served by the same feeder or service in a one-family, two-family or multifamily dwelling. NEC 2017 §220.53 (fastened-in-place appliances) — free NFPA account to read ↗
- Working space in front of a panel must be at least how wide? 30 in or the equipment width, whichever is greater. Rule (NEC 2017 §110.26(A)(2)): the width of the working space in front of electrical equipment must be the width of the equipment or 30 in, whichever is greater. NEC 2017 §110.26(A)(2) (working space width) — free NFPA account to read ↗
- Service disconnecting means must be located? At a readily accessible location nearest the point of entrance of the service conductors. Rule (NEC 2017 §230.70(A)(1)): the service disconnecting means must be installed at a readily accessible location either outside the building or inside nearest the point of entrance of the service conductors. NEC 2017 §230.70(A)(1) (service disconnect location) — free NFPA account to read ↗
Grounding & Bonding 15% of the exam · 23 practice questions
- The grounding electrode conductor to a concrete-encased electrode need not be larger than? 4 AWG copper. Rule (NEC 2017 §250.66(B)): where the grounding electrode conductor (or bonding jumper) is the sole connection to a concrete-encased electrode, that portion is not required to be larger than 4 AWG copper. NEC 2017 §250.66(B) (GEC to concrete-encased electrode) — free NFPA account to read ↗
- The grounding electrode system for a building includes? All electrodes present (water pipe, concrete-encased, rods, ground ring, etc.) bonded together. Rule (NEC 2017 §250.50): all grounding electrodes described in §250.52(A)(1) through (A)(7) that are present at each building or structure must be bonded together to form the grounding electrode system. NEC 2017 §250.50 (grounding electrode system) — free NFPA account to read ↗
- The grounding electrode conductor to a rod electrode need not be larger than? 6 AWG copper. Rule (NEC 2017 §250.66(A)): where the grounding electrode conductor (or a bonding jumper) is the sole connection to a rod, pipe or plate electrode, that portion is not required to be larger than 6 AWG copper or 4 AWG aluminum, regardless of service size. NEC 2017 §250.66(A) (GEC to rod) — free NFPA account to read ↗
Raceways & Boxes 14% of the exam · 19 practice questions
- In walls of combustible material, boxes must be? Flush with the finished surface or projecting. Rule (NEC 2017 §314.20): in walls or ceilings of wood or other combustible surface material, boxes must be flush with the finished surface or project from it. NEC 2017 §314.20 (box setback) — free NFPA account to read ↗
- Raceways exposed to different temperatures (e.g., from inside to outside) must be? Sealed to prevent condensation circulation. Rule (NEC 2017 §300.7(A)): where portions of a raceway or sleeve are known to be subjected to different temperatures and condensation is known to be a problem, as in cold storage areas or where a raceway passes from the interior to the exterior of a building, the raceway or sleeve must be filled with an approved material to prevent the circulation of warm air to a colder section. NEC 2017 §300.7(A) (raceway sealing) — free NFPA account to read ↗
- Maximum conduit fill for three or more conductors? 40%. Rule (NEC 2017 Chapter 9, Table 1): the maximum percent of conduit cross-sectional area that conductors may fill is 53% for one conductor, 31% for two conductors and 40% for over two conductors. Conduit nipples 24 in or shorter may be filled to 60%. NEC 2017 Chapter 9, Table 1 (conduit fill) — free NFPA account to read ↗
Conductors & Cables 11% of the exam · 16 practice questions
- Minimum cover for UF cable direct buried (general)? 24 in. Rule (NEC 2017 §300.5, Table 300.5, Column 1): direct-buried cables or conductors (such as UF) require a minimum cover of 24 in in general locations. Cover is measured from the top of the cable to the finished grade. NEC 2017 Table 300.5 (minimum cover) — free NFPA account to read ↗
- Overcurrent protection for 12 AWG copper is limited to? 20 A. Rule (NEC 2017 §240.4(D)): unless specifically permitted elsewhere (§240.4(E) or (G), such as motor or air-conditioning circuits), overcurrent protection may not exceed 15 A for 14 AWG copper, 20 A for 12 AWG copper and 30 A for 10 AWG copper. NEC 2017 §240.4(D) (small conductor protection) — free NFPA account to read ↗
- Ampacity adjustment is required when more than how many current-carrying conductors are in a raceway or cable? 3. Rule (NEC 2017 §310.15(B)(3)(a)): where the number of current-carrying conductors in a raceway or cable exceeds three, the allowable ampacity of each conductor must be reduced as shown in Table 310.15(B)(3)(a). NEC 2017 §310.15(B)(3)(a) (ampacity adjustment) — free NFPA account to read ↗
Photovoltaics 9% of the exam · 12 practice questions
- Interactive PV inverters automatically stop exporting power when? Utility power is lost (anti-islanding). Rule (NEC 2017 §705.40): upon loss of the primary source (the utility), an electric power production source such as an interactive PV inverter must automatically disconnect from all ungrounded conductors of the primary source and may not reconnect until the primary source is restored. NEC 2017 §705.40 (loss of utility power) — free NFPA account to read ↗
Overcurrent Protection 6% of the exam · 11 practice questions
- A replacement breaker must be? Listed for the panel with the correct type, ampere and interrupting rating. Rule (NEC 2017 §110.3(B) and §110.9): listed equipment must be installed and used according to its listing and labeling instructions. NEC 2017 §110.3(B) (installation per listing) — free NFPA account to read ↗
- Equipment must have an interrupting rating at least equal to? The available fault current at its line terminals. Rule (NEC 2017 §110.9): equipment intended to interrupt current at fault levels (breakers and fuses) must have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. NEC 2017 §110.9 (interrupting rating) — free NFPA account to read ↗
- HACR-rated breakers are used for? Heating, air-conditioning and refrigeration equipment. HACR (Heating, Air-Conditioning and Refrigeration) rated breakers are listed for use with HVAC and refrigeration equipment whose nameplate calls for 'Maximum fuse or HACR circuit breaker.' The equipment nameplate's maximum overcurrent rating and type must be followed (NEC §110.3(B), §440.22).
General Electrical Knowledge 5% of the exam · 6 practice questions
- In a series circuit, the current is? The same through every load. In a series circuit there is only one path, so the same current flows through every load (Kirchhoff's current law).
- The voltage between the two ungrounded conductors of a 120/240 V single-phase service is? 240 V. In simple words: A 120/240 V single-phase, 3-wire service has two hot (ungrounded) wires from opposite ends of the transformer and a neutral (grounded) wire from its center tap; each hot is 120 V to the neutral, and the two hots are 180 degrees apart (opposite), so their voltages add up.
- Power factor is the ratio of? Real power (W) to apparent power (VA). Power factor (PF) = real power (watts) ÷ apparent power (volt-amperes), a number between 0 and 1. Resistive loads have a PF of 1. Inductive loads such as motors and transformers have a PF below 1, so they draw more current than their wattage suggests.
Lighting 5% of the exam · 8 practice questions
- Lighting outlets are required in attics and crawl spaces used for storage or containing equipment, with a switch at? The point of entry. Rule (NEC 2017 §210.70(A)(3)): in attics, underfloor spaces, utility rooms and basements used for storage or containing equipment requiring servicing, at least one lighting outlet containing a switch or controlled by a wall switch must be installed. NEC 2017 §210.70(A)(3) (attic and crawl space lighting) — free NFPA account to read ↗
- Which luminaire is NOT allowed in a clothes closet? Open or partially enclosed incandescent lamp. Rule (NEC 2017 §410.16(B)): incandescent luminaires with open or partially enclosed lamps and pendant luminaires or lampholders are not permitted in clothes closets, because stored clothing can touch a hot bare bulb and ignite. NEC 2017 §410.16(B) (closet luminaires) — free NFPA account to read ↗
- Luminaires in damp or wet locations must be? Listed for damp or wet locations as applicable. Rule (NEC 2017 §410.10(A)): luminaires installed in wet or damp locations must be installed so that water cannot enter or accumulate in wiring compartments, lampholders or other electrical parts. NEC 2017 §410.10(A) (wet and damp luminaires) — free NFPA account to read ↗
Fire Detection & Alarm 5% of the exam · 7 practice questions
- Heat detectors are often used instead of smoke alarms in? Garages and other areas where smoke alarms cause nuisance alarms. Heat detectors respond to a fixed temperature or a rapid rate of temperature rise rather than to smoke particles.
- Multiple smoke alarms in a new dwelling must be? Interconnected so all sound when one activates. Rule (NFPA 72 (2016) §29.8.2; also 2018 IRC §R314.4): where more than one smoke alarm is required within a dwelling unit, the alarms must be interconnected so that activation of one alarm activates all the alarms in the unit. NFPA 72 (2016) Chapter 29 (interconnection of alarms) — free NFPA account to read ↗
- Smoke alarms in new construction must be powered by? The building wiring with battery backup. Rule (2018 IRC §R314.6): smoke alarms must receive their primary power from the building wiring where it is served from a commercial source, and when primary power is interrupted, they must receive power from a battery. 2018 IRC §R314.6 (Smoke alarm power source) ↗
Safety 5% of the exam · 8 practice questions
- Extension cords on construction sites must be? Hard-usage or extra-hard-usage types and in good repair. Rule (OSHA 29 CFR 1926.405(a)(2)(ii)(J)): extension cord sets used with portable electric tools and appliances must be of three-wire type and designed for hard or extra-hard usage (such as types S, ST, SO, SJ, SJT and SJO). OSHA 29 CFR 1926.405 (Wiring methods) ↗
- Before working on a circuit, OSHA lockout/tagout requires? De-energizing, locking and tagging the disconnect, and verifying it's dead. Rule (OSHA 29 CFR 1926.417): controls that are to be deactivated during work on energized or de-energized equipment or circuits must be tagged, and equipment or circuits that are de-energized must be rendered inoperative and have tags attached at all points where they could be energized. OSHA 29 CFR 1926.417 (Lockout and tagging of circuits) ↗
- Before relying on a voltage tester, you should? Test it on a known live source before and after testing the circuit. Before relying on a voltage tester to prove a circuit is dead, use the 'live-dead-live' method: test the meter on a known live source, test the circuit you'll work on, then test the meter again on the known live source.
Special Occupancies & Equipment 3% of the exam · 4 practice questions
- Receptacles that supply pool pump motors must be? GFCI protected. Rule (NEC 2017 §680.21(C) and §680.22(A)): receptacles that provide power for pool pump motors and other circulation and sanitation equipment must be located at least 6 ft from the inside walls of the pool and must have GFCI protection. NEC 2017 §680.21(C), §680.22(A) (pool pump GFCI) — free NFPA account to read ↗
- At least one 125 V receptacle must be located between 6 ft and 20 ft from the inside wall of a permanently installed pool? True. Rule (NEC 2017 §680.22(A)): where a permanently installed pool is installed, at least one 125 V, 15 or 20 A receptacle on a general-purpose branch circuit must be located not less than 6 ft from, and not more than 20 ft from, the inside wall of the pool, and not more than 6-1/2 ft above the floor, platform or grade serving the pool. NEC 2017 §680.22(A) (pool receptacle location) — free NFPA account to read ↗
- Which dwelling locations require GFCI protection for 125 V receptacles (2017 NEC)? Bathrooms, garages, outdoors, crawl spaces, unfinished basements, kitchen countertops, within 6 ft of sinks, laundry areas. Rule (NEC 2017 §210.8(A)): all 125 V, single-phase, 15 and 20 A receptacles installed in these dwelling locations require GFCI protection: bathrooms; garages and accessory buildings with floors at or below grade; outdoors; crawl spaces at or below grade; unfinished portions of basements; kitchens where receptacles serve countertop surfaces; within 6 ft of the top inside edge of a sink bowl; boathouses; within 6 ft of a bathtub or shower stall; and laundry areas. NEC 2017 §210.8(A) (dwelling GFCI) — free NFPA account to read ↗
Motors 3% of the exam · 4 practice questions
- Motor branch-circuit conductors are sized using full-load current from? The NEC tables (430.247–430.250). Rule (NEC 2017 §430.6(A)(1)): the full-load current values in Tables 430.247, 430.248, 430.249 and 430.250 (not the motor nameplate) must be used to determine the ampacity of conductors, the ampere rating of switches and the rating of branch-circuit short-circuit and ground-fault protection. NEC 2017 §430.6(A)(1) (motor FLC from tables) — free NFPA account to read ↗
- A single motor has a full-load current of 20 A from the NEC tables. Minimum branch-circuit conductor ampacity? 25 A. In simple words: Wires feeding a single motor in continuous duty must be able to carry at least 125% of the motor's full-load current, because motors draw extra current and the wire must not overheat. NEC 2017 §430.22 (single motor conductors) — free NFPA account to read ↗
- To reverse a three-phase motor's rotation? Swap any two line leads. A three-phase motor's direction of rotation depends on the phase sequence (A-B-C). Swapping any two of the three line leads reverses the sequence and therefore the rotation. Swapping all three in a rotating order does not change rotation.
Electrical Devices 2% of the exam · 5 practice questions
- New 15 A and 20 A 125 V receptacles in dwellings must be? Tamper-resistant. Rule (NEC 2017 §406.12): in dwelling units, all 15 and 20 A, 125 V and 250 V nonlocking-type receptacles in the areas specified in §210.52 must be listed tamper-resistant receptacles. NEC 2017 §406.12 (tamper-resistant receptacles) — free NFPA account to read ↗
- Receptacles installed in damp or wet locations must be? Listed weather-resistant. Rule (NEC 2017 §406.9): receptacles in damp locations must have an enclosure that is weatherproof when the cover is closed and a plug is not inserted. 15 and 20 A, 125 and 250 V receptacles in wet locations must have an enclosure that is weatherproof whether or not a plug is inserted (an extra-duty 'in-use' cover). NEC 2017 §406.9 (damp and wet location receptacles) — free NFPA account to read ↗
- A grounded conductor must be provided at most switch locations controlling lighting? True (NEC 404.2(C)). Rule (NEC 2017 §404.2(C)): where switches control lighting loads supplied by a grounded general-purpose branch circuit, the grounded (neutral) conductor for the controlled lighting circuit must be installed at the switch location. NEC 2017 §404.2(C) (neutral at switch locations) — free NFPA account to read ↗
Low Voltage 2% of the exam · 4 practice questions
- A doorbell transformer typically supplies? Class 2 low voltage (e.g., 16–24 V). A doorbell transformer steps 120 V down to a low voltage, commonly about 10 to 24 V AC (16 V is typical), and is a listed Class 2 power source, meaning its output current and power are inherently limited.
- Class 2 low-voltage cables (doorbell, thermostat) must be? Separated from power and lighting conductors. Rule (NEC 2017 §725.136): Class 2 and Class 3 circuit conductors (such as doorbell and thermostat wiring) may not be placed in any cable, cable tray, compartment, enclosure, manhole, outlet box, device box, raceway or similar fitting with conductors of electric light, power, Class 1, non-power-limited fire alarm or medium-power network-powered broadband circuits, unless separated by a barrier or as otherwise specifically permitted. NEC 2017 §725.136 (Class 2 separation) — free NFPA account to read ↗
- Low-voltage landscape lighting systems are covered by NEC Article? 411. Rule (NEC 2017 Article 411): low-voltage lighting systems, such as landscape lighting supplied by a listed power supply (transformer), operating at not more than 30 V AC or 60 V DC, are covered by Article 411. NEC 2017 Article 411 (low-voltage lighting) — free NFPA account to read ↗
The Statutes & Rules exam
Most Arizona applicants also take the Statutes & Rules exam. Its sections:
- Licensing & Classifications20%
- Contracts, Advertising & Payment20%
- Qualifying Party & License Upkeep15%
- Bonds & Recovery Fund15%
- Mechanics' Liens15%
- Complaints & Penalties15%
Licensing & Classifications 20% of the exam · 137 practice questions
- An owner may build or improve their own property without a license if the structure is? Intended solely for the owner's occupancy, not for sale or rent. Rule (A.R.S. § 32-1121(A)(5)): owners may build or improve structures on their own property without a license only if the work is intended solely for their own occupancy and not offered for sale or rent. A.R.S. §32-1121 (Persons not required to be licensed) ↗
- The B-3 General Remodeling and Repair license covers? Remodeling and repair of existing residential structures. Rule (A.A.C. R4-9-103, B-3 General Remodeling and Repair): the B-3 license covers remodeling and repair of existing residential structures, including the R-7 carpentry scope. Other trades such as electrical and plumbing must be subcontracted. A.A.C. R4-9-103 (B-3 General Remodeling and Repair), ROC rules p. 11 ↗
Contracts, Advertising & Payment 20% of the exam · 36 practice questions
- Under the Arizona Prompt Pay Act, an owner has how long to approve or object to a progress billing? 14 days. Rule (Arizona Prompt Pay Act, A.R.S. § 32-1182): an owner has 14 days after receiving a progress billing to certify and approve it, or to object in writing. A.R.S. §32-1182 (Progress payments by owner) ↗
- An unlicensed person advertises 'Kitchen remodels — call us!' without the required statement. This violates? Arizona's advertising rules and the consumer fraud act (A.R.S. § 44-1522). Rule (A.R.S. § 32-1121(C) and § 44-1522): an unlicensed person who advertises for work that requires a license, or omits the required 'not a licensed contractor' statement, violates Arizona's advertising rules and commits consumer fraud. A.R.S. §32-1121 (Persons not required to be licensed) ↗
Qualifying Party & License Upkeep 15% of the exam · 51 practice questions
- If the licensee does not replace its qualifying party in time, the license is? Automatically suspended by operation of law. Rule (A.R.S. § 32-1127.01(C)): if the licensee doesn't replace its qualifying party within the 60-day period, the license is automatically suspended by operation of law until a qualified replacement is approved. A.R.S. §32-1127.01 (Qualifying party disassociation) ↗
- Reactivating an inactive license requires? The renewal fee and 30 days' written notice. Rule (A.R.S. § 32-1125.01): to reactivate an inactive license, the licensee gives the registrar 30 days' written notice and pays the renewal fee. No new exam is required. A.R.S. §32-1125.01 (Inactive license) ↗
Bonds & Recovery Fund 15% of the exam · 38 practice questions
- Residential and dual licensees must either join the Residential Contractors' Recovery Fund or post an additional bond of? $200,000. Rule (A.R.S. § 32-1152): residential and dual licensees must either participate in the Residential Contractors' Recovery Fund or post an additional bond of $200,000. A.R.S. §32-1152 (Bonds) ↗
- Recovery Fund actual damages are the reasonable cost to complete the contract and repair defective work? Minus the unpaid contract price. Rule (A.R.S. § 32-1132.01(H)): Recovery Fund actual damages are the reasonable cost to complete the contract and repair defective work, minus any unpaid contract price the owner still owes. A.R.S. §32-1132.01 (Recovery fund damages and limits) ↗
Mechanics' Liens 15% of the exam · 29 practice questions
- If the owner records and serves a notice of completion, a lien must be recorded within? 60 days after the notice. Rule (A.R.S. § 33-993(A)): if the owner records and serves a notice of completion, a lien must be recorded within 60 days after the notice is recorded. A.R.S. §33-993 (Perfecting a lien) ↗
- A preliminary notice includes an estimate of? The total price of labor and materials to be furnished. Rule (A.R.S. § 33-992.01): a preliminary notice must include an estimate of the total price of the labor, materials and equipment the claimant will furnish. A.R.S. §33-992.01 (Preliminary twenty-day notice) ↗
Complaints & Penalties 15% of the exam · 31 practice questions
- The maximum civil penalty for multiple violations committed on the same day is? $2,500. Rule (A.R.S. § 32-1166.01): the Registrar may issue citations with civil penalties to persons who contract without a license. The total civil penalty for all violations committed on the same day may not exceed $2,500. A.R.S. §32-1166.01 (Citations; civil penalties) ↗
- A homeowner who hires an unlicensed contractor generally? Cannot claim from the Recovery Fund. Rule (A.R.S. § 32-1132): the Recovery Fund covers only damage caused by appropriately licensed residential contractors, so a homeowner who hires an unlicensed contractor generally can't claim from it. A.R.S. §32-1132 (Residential contractors' recovery fund) ↗
Questions people ask
What is on the Arizona R-11 Electrical exam?
The exam is weighted by section: Services, Feeders & Branch Circuits 16%, Grounding & Bonding 15%, Raceways & Boxes 14%, Conductors & Cables 11%, Photovoltaics 9%, Overcurrent Protection 6%, General Electrical Knowledge 5%, Lighting 5%, Fire Detection & Alarm 5%, Safety 5%, Special Occupancies & Equipment 3%, Motors 3%, Electrical Devices 2%, Low Voltage 2%.
What is the format of the Arizona R-11 Electrical exam?
110 questions, 240 minutes, 70% to pass (PSI). Open book: 2017 NEC, NFPA 72 (2016) and 29 CFR 1926.
What should I study first for the Arizona R-11 Electrical exam?
Start with the largest sections, which carry the most points: Services, Feeders & Branch Circuits (16%), Grounding & Bonding (15%), Raceways & Boxes (14%). Then take a timed mock exam and spend extra time on whatever scored lowest.
Do I also need the Statutes & Rules exam?
Most applicants for this license also take the Statutes & Rules exam. It is included with this course, so you can practice both.
Where can I practice for the Arizona R-11 Electrical exam?
LicenseExamReady has 478 practice questions for the Arizona R-11 Electrical exam and the Statutes & Rules exam, full mock exams weighted like the real test, explanations that cite the code section or rule, and a readiness score. New accounts get a free 3-day trial.
Are practice questions the same as the real exam?
No. Licensing boards keep their exams confidential. Good practice questions are written from the official exam outline and code books and teach the rule behind each answer.
Practice for the Arizona R-11 Electrical exam
478 practice questions, full-length timed mock exams weighted like the real test, explanations with sources, and a readiness score that shows when you're ready to book the exam.
LicenseExamReady is an independent study tool, not affiliated with Arizona Registrar of Contractors. How our questions are made.